Protective wire tester
P 3301 D
The earth bond tester P 3301 allows protective conductor tests and continuity tests which are in accordance with many standards (IEC, EN, UL, BS, VDE, etc.). To generate the high test current an electronic alternating current source is available, programmable between 10 AAC and 30 AAC.
The design of these testers meets all the necessary requirements, i.e. from hand operation to automatic protocolling to a fully automatic system application. Software packages for remote control support complete concepts as well as OEM users.
Special attention has been paid to a user-friendly operation using a multiple line LC-display and function keys with plain text. Available is a programme memory for 100 programmes/setups with 100 steps per programme/setup. The included WINDOWS software allows the creation and loading of test programmes on your PC. Via a simple WINDOWS software programme (option) remote control by PC is possible. The printer interface allows standard protocols of all parameters as well as of the test and measurement results.
As the continuity test and the protective conductor test are automatically applied to the DUT, it need only be connected once.
| Technische Daten | |
| Hochspannungstest - Potential - Sicherheitsstrombegrenzung | 1500 VDC / 4 mA ja |
| Isolationstest - Potential - Sicherheitsstrombegrenzung | 500 VDC / 50 MOhm frei ja |
| Schutzleitertest - Widerstandsmessung (EN 60 335)
- Spannungsmessung (EN 60 204) - Leerlaufspannung | max. 30 AAC bis 20 AAC, max. 500 mOhm 0 - 4 VAC 6 V und 12 V |
| Gehäuse | 14" / 3 HE |
| Netz | 230 V / 50 Hz oder 115 V / 60 Hz |
| Technical data | |
| earth bond test resistance measurement (EN 60 335)
voltage measurement (EN 60 204) no-load voltage | 10 - 30 AAC till 20 AAC, max. 500 mOhm 0 - 4 VAC 6 V and 12 V |
| continuity test | 22 VDC / 0,5 A |
| plug-in | 14" / 3 HU |
| power supply | 230 V / 50 Hz or 115 V / 60 Hz |
- conforms to CE, in accordance with EN 50 191
- 2 in 1 tester
- automatic test process
- internal change-over for all tests with single connection of DUT
- dwell time 0.1 up to 99.9 seconds
- visual and audible alarm
- window comparator for setups
- micro processor controlled
- 100 programmes/setups with 100 steps per programme/setup
- internal clock / calendar
- LC-display with 4 * 20 characters
- PLC remote control interface
- PLC memory recall interface
- PC remote control interface
- PC setup software included
Options
- PC remote control software
Accessories
- test enclosure
- protective wire test probe
- test dummy

